Cast resin Transformers
 

SPECIFICATION

  • Cast resin dry type transformer 11kV/433 or 415V,3 phase,50 Hz
  • Off load tap links ± 5% in steps of 2.5% (Optional)
  • HV delta connected ,LV star connected
  • Dyn 11 vector group
  • Ip-23 metal enclosure powder coated RAL 7032
  • Class F insulation
  • 75kV impulse withstand standard
  • IN ACCORDANCE WITH IEC 60076-11 /IS 11171 / IEC 726
  • Continuous duty cycle
  • Natural air cooling & forced air cooling

SUPERIOR FEATURES OF TRIO TEC CAST RESIN TRANSFORMERS

  • Low loss, low maintenance cost
  • Space saving compact design
  • Superior short circuit strength
  • Long life expectancy
  • Fire resistance and self – extinguishing
  • Easy installation and connection
  • Free from partial discharge
  • Moisture proof
  • Smooth surfaces of the moulded HV & LV coils minimize the accumulation of air dust and improve effective cooling
  • Higher output can be achieved with integrally arranged forced cooling arrangement
  • The HV & LV coils are supported on the top and bottom with epoxy blocks cushioned with resilient parts to permit expansion and contraction

CORES

  • The cores used are manufactured from high quality, low loss, grain oriented cold rolled silicon steel sheets, which are all finished according to slitting and length cutting lines by auto numerical control cutting machines
  • The choice and the grade and the cutting pattern and the method of assembly minimized the loss level and the no-load current with the effect of very low noise level
  • Core surfaces are sealed with insulating resin to prevent from moisture and corrosion

HV COILS

  • DISC winding is used for HV coils
  • H.V. windings are made of double enameled class F copper conductors with DuPont make NOMEX paper as inter layer insulation
  • The HV discs are vacuum pressure impregnated with epoxy resin before casting which provides very low partial discharge and avoid ageing

LV COILS

  • LV windings are made of fiberglass insulated copper strip of various size confirming to class H insulation
  • The wound coil is casted with filled epoxy resin and polymerized in an oven, to withstand safely the electrodynamic forces present in a short circuit

TESTING OF TRANSFORMERS

A particular attention is always given to the testing of the transformer, which is done as per IEC 60076-11 standard


ROUTINE TEST

  • Measurement of winding resistance
  • Measurement of voltage ratio
  • Measurement of short circuit impedance
  • Measurement of load losses
  • Measurement of no load loss and current
  • Insulation measurement
  • Double volt double frequency (DVDF) test